The Pipe Behind the Wall Fails Where the Water Stands Still
The grade on the schedule is the last decision that matters
A building water-supply pipe is bought quietly. Nobody sees it again until it leaks. The tube pages in the product range list their applications plainly, and water supplying sits between construction and upholstery, which is honest about how ordinary the duty usually is. The interesting part of the decision is not whether stainless belongs in a wall; it is which stainless, which wall, and what happens the night the circulation pump stops.
Pressure is almost never the problem
Run the hoop stress for a domestic riser. A 25 mm outside diameter tube with a 1.5 mm wall, held at 1.0 MPa, carries a membrane stress of 1.0 times 25 divided by twice 1.5, or 8.3 MPa. The annealed 304L tube on the 304 and 304L seamless pipe page carries a minimum yield around 30,000 psi, which is roughly 207 MPa. The wall is working at about four per cent of yield. A pressure-tight tube would need a fraction of a millimetre of steel.
The remaining 1.4 mm is there for press-forming the ends, for the weld, for the plumber who steps on the riser, and for the slow chemistry of the water. That is why the schedule of tests matters more than the schedule of thickness: the works test on the stainless pipe page runs a squash test, an extended test and a water pressure test, and a tube that has passed those has already proven more than the plumbing will ever ask of it.
Chloride picks the grade
A common screening approach, not a code, runs like this: below roughly 200 mg per litre of chloride and below 30 C, a 304-family tube with 18 to 20 per cent chromium and 8 to 13 per cent nickel gives long service. Above either line, move to molybdenum. 316L carries between 2 and 3 per cent of it, with carbon held near 0.03 so welds stay resistant; the 316L grade data puts the molybdenum in the same band. This is the default hot-water and recirculation grade.
Two steps further, the ladder stops being incremental. The 317LMN tube page describes an austenitic grade with 4 to 5 per cent molybdenum and a deliberate nitrogen addition specified from 0.10 up to 0.20 per cent, grades it above both 316L and 317L in water, and places it at the top of the standard stainless family for aqueous duty. That is the grade for coastal supply water or a building on a brackish well. For the highest duty, the duplex 2205 seamless pipe and the S32205 pipe under ASTM A790 bring a yield near double an annealed austenitic, so a thinner wall does the same structural work; the S31803 pipe covers the same family in the leaner composition.
Seamless or welded, decided by the schedule not the water
For a domestic system the seamless-versus-welded choice is economic rather than hydraulic. The pipe pages are candid about the trade: the thicker the wall, the more economical and practical the product, while the thinner the wall, the greater the processing cost, and seamless tube shows its advantage in high-pressure, high-strength structural duty. A 1.5 mm wall riser is squarely in welded-tube territory, where a continuous strip is formed and seam-welded at a rate no pierce-and-rolling line can match; a 6 mm wall main feeding a fire service is a different conversation. What the buyer should insist on either way is full-length eddy-current testing of the weld, because the hoop arithmetic above only holds for a wall that is actually there.
Hot water moves; the pipe has to allow for it
An austenitic tube grows 17.2 microns per metre for each kelvin of rise. A 20 m riser that swings 45 K between a cold commissioning morning and full recirculation gets longer by 15.5 mm, and that movement has to go somewhere: a loop, an offset, or a bellows at the riser foot. A straight run clamped rigid at both ends transfers the strain into the fittings instead, and fittings are the thinnest, most worked metal in the system.
Temperatures beyond domestic service are a different catalogue. The 310S pipe exists for furnace duty, and specifying it for a plumbing run is paying for chromium nobody asked to use.
The failure happens at zero velocity
Pitting in potable service almost always starts where the water stands still: dead legs, stub outs, a section of pipe behind a closed valve. Flowing water keeps the passive film repaired and the chloramine moving; stagnant water lets a crevice form its own chemistry. A sensible design velocity sits between 0.5 and 2 m per second, which flushes the tube without eroding the weld roots.
This is also where the cheaper grades fail. 201 stainless was developed to conserve nickel, and the composition shows it: 16 to 18 per cent chromium, nickel 3.5 to 5.5, manganese 5.5 to 7.5, and no molybdenum at all. At 685 MPa tensile it is a strong tube, and in cold, treated, continuously moving water it can hold for decades. In a hot chlorinated dead leg it is the first grade to pit, which is why the 201 coil belongs in decorative and dry duty rather than behind a wall.
General-service welded tube such as the 302 tube, made from coil by automated spiral welding and sold for transporting liquids and gases, carries 17 to 19 per cent chromium and 8 to 10 per cent nickel; it is the honest mid-grade where the water is tame and the budget is real.
The dead-leg problem is designed out, not materialled out. Every branch longer than a few diametres that ends in a closed valve is a future chemistry experiment, and so is the stub left behind when a fixture is moved during refurbishment. Commissions that record which runs are live, and colour-code the isolations, remove more risk than the grade ladder does.
Galvanic pairs and visible pipework
Stainless against brass or bronze fittings is a stable couple in supply water. Stainless against a bare carbon-steel clamp in a sweating plant room is not; the clamp corrodes and stains the tube it supports. Sleeved hangers cost minutes at installation. Where the riser is architectural rather than buried, the square stainless tube, 10 by 10 up to 100 by 100 mm in lengths to 12 m, encloses the run and takes the bracket duty itself.
What the enquiry should state
Grade and wall, the chloride and temperature of the water, the velocity the system will actually run at, and the standards: ASTM A213, A312 and A269 cover the austenitic tube families on the large-diameter thick-wall pipe page, A778 and A789 the welded specialities, A790 the duplex. Wall tolerance is plus or minus one per cent on the works figures. Ask for annealed and pickled delivery and the full test pack, the way the 347H seamless pipe page lists flattening, flaring and chemical tests as routine.
Then state the one thing most orders omit: where the dead legs will be. The grade survives the water that moves; the specification is really written for the water that does not.