A Partition Is Sized by Deflection, Not by Strength
A partition is bought by area and judged by how straight it stays
A non-loadbearing partition is quoted by the square metre, delivered as a bundle of thin galvanized studs, and judged years later by whether a door still closes cleanly. Nothing in that wall is chosen for its strength. A three metre wall of 0.55 mm C-studs at 600 mm centres, clad both sides in 12.5 mm board, has ample steel to stand up and lacks only stiffness. The governing number is a deflection limit, written for the finish, not the frame.
The lateral load is small; the allowable movement is smaller
Interior partitions are designed against a modest lateral pressure. Half a kilopascal covers people leaning, a door slam, and the pressure difference a ventilation system puts across a wall. At 600 mm centres each stud carries a 0.6 m strip, so 0.5 kPa becomes 0.3 kN per metre of height, or 0.3 N/mm, over a 3,000 mm span.
The finish sets the limit. Brittle board and tiled faces are held to span over 360, which is 8.3 mm here; a forgiving paint finish allows span over 240, or 12.5 mm. Treat the stud as a simply supported beam, take E as 200,000 N/mm2 and the second moment of area of a 50 mm C-section in 0.55 mm strip as roughly 80,000 mm4, and five times the load times the fourth power of the span over 384 E I gives about 19.8 mm. The bare stud misses even the easier limit by half again.
The board becomes structure once the screws go in
Which is why a partition is never left as bare studs. Two faces of board, screwed at 300 mm centres in the field and 200 mm at the edges, turn the open C into something close to a closed box: the sheeting stops the free flange twisting and suppresses the lateral-torsional buckling a thin open section is prone to. Gypsum is far softer than steel, but it supplies restraint, and restraint lets the stud reach its calculated value. The screw pattern is a structural detail, not a fixing schedule. Joints are staggered between faces so a seam cannot act as a hinge, and the perimeter is sealed: a 3 mm gap at the head leaks air and sound.
Strength was never the constraint
Run the same load through a stress check: The maximum moment on a uniformly loaded stud is q L squared over eight, or 337,500 N.mm on these numbers. With a 50 mm deep section the elastic modulus is about 3,200 cubic millimetres, so the extreme fibre sees roughly 105 MPa. The structural grades behind A653 structural coil start well above that, and carbon content across that family runs from 0.05 to 0.70 per cent. There is two to three times the strength the wall needs. Adding gauge is the expensive way to buy eight millimetres of deflection; closing the centres to 400 mm, or adding a board layer, is the cheap one. Sized by strength, the wall is heavier, dearer and no straighter.
The head detail decides whether the wall survives the building moving
A partition stands on a floor track and dies at the head. The slab above deflects, creeps over years, and moves with the frame in wind; fix the top track rigidly and that movement goes straight into the studs and the joints crack. A deflection head leaves 10 to 15 mm of clearance and uses a sliding connection that restrains the wall sideways while letting the slab move vertically. A suspended ceiling is the opposite: hangers in tension, the grid carrying its own weight, while a partition carries almost no vertical load beyond itself.
The stud is roll-formed. Cut blanks come off the shearing line; the plate bending route covers the 180 degree and double-layer folds that stiffen the lip of a C; and service holes go through the web by punching, which the processing page calls a mass-production method for repeated holes of one size. Put them in the middle third of the web, never at a cut end.
Sound and fire are board problems
Acoustic performance follows mass and decoupling, not steel grade. Two 12.5 mm boards either side of a 50 mm cavity with mineral wool reach the low forties in dB if the joints are sealed; one row of studs bridging both faces loses several dB, because the steel is a direct path for vibration. A resilient bar on one face, or two staggered rows, breaks that bridge. Fire is the same argument in reverse: a 0.55 mm section has almost no thermal mass, so the board, with its bound water, is the fire layer and the steel is what gets protected. A heavier zinc coating changes neither figure.
Door openings and tall walls need their own section
Openings break the repetition the calculation assumes. A door jamb takes the leaf weight plus the closing impact, so the stud beside it is doubled into a boxed section and a header passes the load back into the neighbouring studs. Past about 3.6 m the same 0.55 mm C at 600 mm stops working, because deflection grows with the fourth power of the span and 3.6 against 3.0 m is a factor of just over two. Tall partitions move to a deeper section, a thicker strip, or closer centres. Anything hung off the face needs a backing plate fixed into the studs, not a cavity fixing into 12.5 mm of gypsum.
Coating mass is a dry-interior decision
Inside a conditioned building the corrosion load is low. Electro-galvanized SECCN2 sheet and its SECCN5 sibling are sold at 40, 60 or 80 grams per square metre; 80 grams works out near 5.6 micrometres on each face, enough for a dry cavity. Where the wall backs onto an external leaf, a wet room, or unconditioned plant space, the Z275 coil range up to 275 grams gives roughly nineteen micrometres a side, and the SGCC galvanized sheet list runs from 30 to 600 grams for the same reason. SGCC is also the page naming light steel keel explicitly among cold-formed articles. Do not galvanize the finished stud: the hot-dipped route immerses the part at around 500 degrees and distorts 0.55 mm strip. Coat the strip first, form it afterwards, and paint the cut ends zinc-rich.
What the drawing has to say
The enquiry should name section depth and strip thickness rather than "50 mm stud", the centres, board layers, screw pattern, head clearance, and coating mass in grams per square metre. The galvanized processing range and the TDC51D prepainted coil cover cut, punched and folded studs that arrive as parts instead of stock, the galvanized plate list covers backing plates for jambs and hung loads, and the final surface treatment belongs on the drawing as its own line. Read the zinc mass off the certificate in grams, then confirm it on delivered studs with a magnetic gauge. On site the acceptance tool is a two metre straightedge and a feeler gauge under raking light: a wall that passes closes its doors; one that fails shows every joint within a year.