A Bore Is Sized by Friction, Not by Its Pressure Rating
Fifty cubic metres an hour down a hundred metres
Take a water line carrying 50 cubic metres an hour, 13.9 litres a second, over a 100 metre run. Two quotations arrive. One is NPS 4 schedule 40, 114.3 mm outside and 6.02 mm wall, a 102.3 mm bore; the other NPS 6 schedule 40, 168.3 mm outside and 7.11 mm wall, 154.1 mm bore. Both pass the pressure check with margin, and that is the last useful thing it says. The A53 specification runs from half inch NB to 36 inch NB in walls of 3 to 12 mm, with SCH 40 through XXS as wall series, and names steam, water and gas line pipes among its duties. Its grades step from 48,000 psi minimum tensile up to 70,000, with 60,000 in between. Neither figure tells the buyer what the pump costs to run.
The velocity the pump has to live with
Flow area is pi over four times the bore squared. At 102.3 mm that is 8,213 square millimetres, so the water moves at 1.69 metres a second. At 154.1 mm the area is 18,646 square millimetres and velocity falls to 0.745. Reynolds number is density times velocity times bore over viscosity; at 1,000 kilograms per cubic metre and one millipascal second the lines sit near 173,000 and 115,000, both fully turbulent. A 304L listing covering 0.08 to 170 mm walls and 3 to 2,200 mm outside diameters contains these sizes; the round tube programme, thicknesses of 0.5 to 75 mm, lists water supplying among its applications and puts squash, extended and water pressure tests in the test line. None of those tests measures the head the line eats.
Diameter is raised to the fifth
Friction loss is f times length over bore times density times velocity squared over two. Take f as 0.020 for commercial steel. On the 102.3 mm bore that is 0.020 times 100 over 0.1023 times 1,430 pascals of velocity head, 28.0 kPa. On the 154.1 mm bore the velocity head is 277 pascals and the loss 3.6 kPa. At fixed flow the loss goes as bore to the minus fifth, so a bore 1.507 times wider divides it by 7.8. That is the 28.0 to 3.6 ratio. The API 5L range from DN6 to DN1200, 4 to 1,219 mm outside and 1 to 60 mm wall, makes both bores, as does the large-diameter programme up to 2,500 mm outside with walls to 150 mm. A size row lists what can be rolled, not a hydraulic answer.
What the pump actually pays
Hydraulic power is flow times pressure loss; shaft power is that over efficiency. At 70 per cent the narrow line takes 0.01389 times 28,000 over 0.70, about 555 W. The wide line takes 71 W. The 480 W difference runs whenever the line runs; across 8,000 hours a year that is nearly 3,900 kilowatt-hours. Steel tells the other half. A thin-wall tube weighs close to pi times outside minus wall times wall times 7,850, which gives 16.1 kilograms a metre for NPS 4 and 28.3 for NPS 6, or 1.61 and 2.83 tonnes over the run. The extra 1.22 tonnes is bought once; the electricity is bought every year. The A53 supply page and the welded against seamless comparison settle how the pipe is made, not the bore.
Fittings are not a rounding error
Six 90 degree bends at K of 0.9, two gate valves at 0.15 and one outlet at 1.0 add to 6.7 velocity heads. On the small bore that is 6.7 times 1,430 pascals, 9.6 kPa, a third of the straight-pipe loss. On the large bore it is 1.9 kPa, better than half of the 3.6 kPa from the straight run. Upsizing does not shrink fittings in proportion, so a generous bore can disappoint at the gauge. Each bend adds K times bore over f of straight tube, 4.6 m on the small line and 6.9 m on the large. Bending work and fabricated weldments set the real radius of those bends, and square tube frames with punched fixing slots hold the fittings where the drawing wants them.
The bore shrinks while the pipe sits there
Scale or a roughened internal film eats diameter, and diameter sits in the denominator five times. One millimetre of deposit on the 102.3 mm bore takes it to 100.3, a 2 per cent loss that raises friction loss by about 10 per cent. The same millimetre on the larger bore is a 1.3 per cent loss and about 7 per cent more friction. New commercial steel starts near 0.045 mm equivalent roughness; a line aged to 0.5 mm can push f from 0.020 towards 0.028, another 40 per cent on the bill. A lined bore is smoother, and permitted outside-diameter tolerances of 0.4, 0.79, 1.59 and 2.38 mm are tight against a decade of deposit. Where the water attacks the wall, the duplex seamless option and the 317LMN tube keep the bore closer to the design case.
Where the schedule helps and where it does not
A schedule indexes a wall to a nominal size. It protects against pressure and houses the corrosion allowance; it says nothing about flow. The A106 wall tolerance of plus or minus 12.5 per cent is a manufacturing band, and the flattening, flaring and water pressure tests prove the boundary, not the throughput. A hydrostatic test at 1.5 times design pressure can pass on a line that loses a third of the pump head to friction. The A53 table picks a wall; the flow sheet picks a bore, and the two are rarely opened together.
Grade decides how long the bore stays that size
Fresh pipe of any grade has much the same hydraulic roughness, so a grade change buys nothing on day one. It buys the years before pitting or scale moves the roughness and bore away from the design case. The 310S pipe for hot service, the 316L coil and the processed galvanized parts serve that longer argument, not the friction sum. Read the 310S sheet with 200 GPa in tension and 205 MPa minimum yield for strength, and the 201 sheet at 197 GPa for stiffness. Neither modulus appears in Darcy's expression, which is why a stronger grade on an undersized bore still needs the same pump.
Put the hydraulic line on the order
State the design flow, the density and viscosity of what actually moves, and the permitted pressure loss or the head the pump can spare. Give the straight length and a fitting schedule with elbow radii, because those K values are not a footnote. Give bore, not nominal size alone, and say whether the figure is new or fouled. Name the internal finish or lining, the roughness it is credited with, and the allowance for scale. Order the support steel and cut bracket work on the same drawing, since a wider bore is heavier. Ask for the hydrostatic record and a cleaning or pigging step as separate lines. A certificate carries tensile and test pressure; only the drawing can show 28 kPa against 3.6 kPa, the number the pump reads for the life of the plant.